 [XM8171]  Pipeline CO2 sensors

XM8171

Technical Parameters

Technical parameterParameter value
BrandXUNCHIP
CO2 range0~5000ppm
CO2 accuracy±100ppm
InterfaceRS485/4-20mA/DC0-5V
PowerDC6~24V 1A
Running temperature-30~80℃
Working humidity5%RH~90%RH

Product Selection

    Product DesignRS485,4-20mA,DC0-5VMultiple output methods, the products are divided into the following models depending on the output method.
Product model output method
XM8171BRS485总线
XM8171M4-20mA
XM8171V5DC0-5V

Product Size

XM8171 XM8171 XM8171 XM8171 XM8171 XM8171

Why choose this product?

XM8171 XM8171 XM8171 XM8171

How to use?

XM8171

Product List

XM8171

Pictures

XM8171 XM8171 XM8171

Communication Protocol

    The product uses the RS485 MODBUS-RTU standard protocol format, and all operation or reply commands are in hexadecimal data. When the device leaves the factory, the default device address is 1, and the default baud rate is: for modules and non-recording instruments: 9600, 8, n, 1 (for the recorder series products, the default is: 115200, 8, n, 1).
1. Read data (Function code 0x03)
    The inquiry frame (in hexadecimal). Example of sending: To query 1 piece of data of device No. 1, the host computer sends the command: 01 03 00 00 00 01 84 0A .
Address Function code Starting address Data length Checksum
010300 0000 0184 0A
    For a correct inquiry frame, the device will respond with data: 01 03 02 02 18 B9 2E , and the response format is:
Address Function code LengthData 1 Checksum
0103 0202 18 B9 2E
    Data description: The data in the command is in hexadecimal. Taking Data 1 as an example, 02 18 converted to decimal value is 536. Assuming the data magnification factor is 100, then the true value is 536/100 = 5.36, and the others can be deduced by analogy.
2. Common Data Address Table
Configuration Address Register Address Register Description Data Type Value Range
4000100 00carbon dioxideRead Only0~65535
4010100 64 Model Code Read-only 0~59999
4010200 65 Total Number of Measuring Points Read-only 1~1600
4010300 66 Device Address Read/Write 1~249
4010400 67 Baud Rate Read/Write 0~6
4010500 68 Communication Mode Read/Write 1 Query
2 Active Upload4010600 69 Protocol Type Read/Write
1 MODBUS-RTU Others Unused

  For example, the range is 400~5000ppm, the analog output is 4~20mA current signal, carbon dioxide and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is carbon dioxide range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read carbon dioxide value, and C is the calculated current value. The list of commonly used values is as follows:
current(mA)carbon dioxideValue (ppm) Calculation Process
4400.0(5000-400)*(4-4)÷(20-4)+400
5687.5(5000-400)*(5-4)÷(20-4)+400
6975.0(5000-400)*(6-4)÷(20-4)+400
71262.5(5000-400)*(7-4)÷(20-4)+400
81550.0(5000-400)*(8-4)÷(20-4)+400
91837.5(5000-400)*(9-4)÷(20-4)+400
102125.0(5000-400)*(10-4)÷(20-4)+400
112412.5(5000-400)*(11-4)÷(20-4)+400
122700.0(5000-400)*(12-4)÷(20-4)+400
132987.5(5000-400)*(13-4)÷(20-4)+400
143275.0(5000-400)*(14-4)÷(20-4)+400
153562.5(5000-400)*(15-4)÷(20-4)+400
163850.0(5000-400)*(16-4)÷(20-4)+400
174137.5(5000-400)*(17-4)÷(20-4)+400
184425.0(5000-400)*(18-4)÷(20-4)+400
194712.5(5000-400)*(19-4)÷(20-4)+400
205000.0(5000-400)*(20-4)÷(20-4)+400
    As shown in the above formula, when measuring 8mA, current current is 1154ppm。
  For example, the range is 400~5000ppm, the analog output is 0~5V DC0-5Vvoltage signal, carbon dioxide and DC0-5Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is carbon dioxide range upper limit, A1 is the lower limit of the range, B2 is DC0-5Vvoltage output range upper limit, B1 is the lower limit, X is the currently read carbon dioxide value, and C is the calculated DC0-5Vvoltage value. The list of commonly used values is as follows:
DC0-5Vvoltage(V)carbon dioxideValue (ppm) Calculation Process
0400.0(5000-400)*(0-0)÷(5-0)+400
11320.0(5000-400)*(1-0)÷(5-0)+400
22240.0(5000-400)*(2-0)÷(5-0)+400
33160.0(5000-400)*(3-0)÷(5-0)+400
44080.0(5000-400)*(4-0)÷(5-0)+400
55000.0(5000-400)*(5-0)÷(5-0)+400
    As shown in the above formula, when measuring 2.5V, current DC0-5Vvoltage is 2300ppm。
software for test product
After downloading, please read the readme.txt documentation

-RV1000- DEGBUG AND TEST SOFTWARE

software for test product
After downloading, please read the readme.txt documentation

[RV1000] DEGBUG AND TEST SOFTWARE

Data and Software

 Online shop 

 Contact Online 

Email: sale@sonbest.com

TYPE: XM8171

WeChat: 13918126020

SKYPE: SOOBUU

Phone: +86-021-66862075

QQ1: 71182854 QQ2:613035997