 [XY2012]  Touch Screen Multi-channel Temperature and Humidity Recorder

XY2012

Technical Parameters

Technical parameter Parameter value
Brand XUNCHIP
Temperature measuring range -30℃~80℃
Temperature measuring accuracy ±0.5℃ @25℃
Communication Interface RS485
Default baud rate 9600 8 n 1
Power DC12~24V 1A
Running temperature -30~80℃
Working humidity 5%RH~90%RH

Product Size

XY2012

Wiring instructions

Why choose this product?

XY2012

Why choose this product?

XY2012 XY2012 XY2012

How to use?

XY2012

Product List

XY2012

Pictures

XY2012 XY2012 XY2012 XY2012

Communication Protocol

    The product uses the RS485 MODBUS-RTU standard protocol format, and all operation or reply commands are in hexadecimal data. When the device leaves the factory, the default device address is 1, and the default baud rate is: for modules and non-recording instruments: 9600, 8, n, 1 (for the recorder series products, the default is: 115200, 8, n, 1).
1. Read data (Function code 0x03)
    The inquiry frame (in hexadecimal). Example of sending: To query 1 piece of data of device No. 1, the host computer sends the command: 01 03 00 00 00 02 C4 0B .
Address Function code Starting address Data length Checksum
01 03 00 00 00 02 C4 0B
    For a correct inquiry frame, the device will respond with data: 01 03 04 02 19 00 00 2A 4C , and the response format is:
Address Function code Length Data 1 Data 2 Checksum
01 03 04 02 18 02 19 2A 4C
    Data description: The data in the command is in hexadecimal. Taking Data 1 as an example, 02 18 converted to decimal value is 536. Assuming the data magnification factor is 100, then the true value is 536/100 = 5.36, and the others can be deduced by analogy.
2. Common Data Address Table
Configuration Address Register Address Register Description Data Type Value Range
40001 00 00 temperature Read Only 0~65535
40002 00 01 humidity Read Only 0~65535
40101 00 64 Model Code Read-only 0~59999
40102 00 65 Total Number of Measuring Points Read-only 1~1600
40103 00 66 Device Address Read/Write 1~249
40104 00 67 Baud Rate Read/Write 0~6
40105 00 68 Communication Mode Read/Write 1 Query
2 Active Upload 40106 00 69 Protocol Type Read/Write
1 MODBUS-RTU Others Unused

 